VIQUA SHF
Model | Flow at 40 mJ/cm² | UV chamber dimensions (cm) |
|---|---|---|
SHF-140 | 470 L/min | 86.4 × 15.2 × 35.6 |
SHF-180 | 600 L/min | 107.3 × 15.2 × 35.6 |
SHF-290 | 813 L/min | 108 × 20.3 × 43.5 |
SHF flow values apply at 95% UV transmittance (UVT), 20 °C and end-of-lamp-life output.
The VIQUA SHF family brings several UV lamps together in a 316L stainless-steel chamber. SHF-140 and SHF-180 contain four lamps; SHF-290 contains five. The three models provide reference flows of 470, 600 and 813 L/min respectively at 40 mJ/cm².
-
Model / UV flow at 40 mJ/cm²
-
Reference UV transmittance (UVT)
-
Reference test temperature
-
Lamp condition for rated flow
-
Manufacturer
-
Water temperature
-
Maximum operating pressure
-
Chamber material